Generator Frequency Drift | |||
Post Reply | Forum |
Posted by: matin ® 02/09/2005, 02:18:37 Author Profile Mail author Edit |
I have in my facility an ABC 950 KWe dual fuel engine the governor installed is hienzmann whats happening is that is that the generator frequency increases to 51.50 hz on its own at all load positions we try to reduce the speed of the engine but after some time it again increases to the same value i cant understand why and niether does the manufacturer can any body suggest some thing
|
Post Reply | Recommend | Alert | View All | | Next | |
Replies to this message |
Re: Generator Frequency Drift | |||
Re: Generator Frequency Drift -- matin | Post Reply | Top of thread | Forum |
Posted by: randykimball ® 02/09/2005, 21:06:06 Author Profile Mail author Edit |
Does this a mechanical governor?
It sounds like linkage hang-up to me. If it gets a demand for highter power then for less power and does not reduce fuel input enough, (due to hanging linkages or worn pivot bushings) it will result in an increased RPM. The reverse could be true, it could cause a reduced RPM. ...or it could hunt up and down in RPM as it fights slack or binding linkages. The worst suggestion of your lifetime may be the catalyst to the grandest idea of the century, never let suggestions go unsaid nor fail to listen to them. |
Post Reply | Recommend | Alert | Where am I? Original Top of thread | | | |
Re: Generator Frequency Drift | |||
Re: Re: Generator Frequency Drift -- randykimball | Post Reply | Top of thread | Forum |
Posted by: matin ® 02/11/2005, 09:36:26 Author Profile Mail author Edit |
No it has an electronic governor hienzman and all the linkages are ok and there is no problem of hunting but the when the frequency increase it doesnot go down it get stuck at 51.50 hz and moves up and down 1 percent as the load changes as if it looks like the governor seems to work at 50 hz but actualy working at 51.50 hz |
Post Reply | Recommend | Alert | Where am I? Original Top of thread |