Working Distances Arc-Flash Calculations per. IEEE 1584-2018
Electrical and Electronics Design and Engineering
Typical Working Distances For Arc-Flash Calculations per. IEEE 1584-2018
Arc-flash design protection is normally based the incident energy level of the working person’s head and torso at the working distance. Typical working distances can be found in the Table below based on the class of equipment. The working distance is used in calculating the incident energy. Alternate working distances may be used depending on the task being performed.
Classes of equipment and typical bus gaps
Equipment Class
|
Working Distance
|
|
SI units |
Imperial units
(in) |
|
15 kV switchgear
|
914.4
|
36
|
15 kV MCC
|
914.4
|
36
|
5 kV switchgear
|
914.4
|
36
|
5 kV MCC
|
914.4
|
36
|
Low-voltage switchgear
|
609.6
|
24
|
Shallow low-voltage
MCCs and panelboards |
457.2
|
18
|
Deep low-voltage
MCCs and panelboards |
457.2
|
18
|
Cable junction box
|
457.2
|
18
|
Reference:
IEEE 1584-2018