IEEE 1584-2018 Electrical Bus Gaps Typical by Enclosure Size
Electrical and Electronics Design and Engineering
IEEE 1584-2018 Electrical Bus Gaps Typical by Enclosure Size
Related
- Arc Flash Hazard Calculations Procedure and Considerations For Medium Voltage System
- Electrode Configuration in Equipment
- Incident Energy Equations and Calculator
- Enclosure Size Equivalent Height and Width Correction Factor
This table relates voltage class, gaps, and enclosure sizes per IEEE 1584-2018. The enclosure sizes can be used to derive the enclosure size, incident energy correction factor.
Classes of equipment and typical bus gaps
Equipment class |
Typical bus gaps (mm) |
Enclosure Size (H × W × D) |
|
SI units (metric) |
Imperial units |
||
15 kV switchgear |
152 |
1143 mm × 762 mm × 762 mm |
45 in × 30 in × 30 in |
15 kV MCC |
152 |
914.4 mm × 914.4 mm × 914.4 mm |
36 in × 36 in × 36 in |
5 kV switchgear |
104 |
914.4 mm × 914.4 mm × 914.4 mm |
36 in × 36 in × 36 in |
5 kV switchgear |
104 |
1143 mm × 762 mm × 762 mm |
45 in × 30 in × 30 in |
5 kV MCC |
104 |
660.4 mm × 660.4 mm × 660.4 mm |
26 in × 26 in × 26 in |
Low-voltage switchgear |
32 |
508 mm × 508 mm × 508 mm |
20 in × 20 in × 20 in |
Shallow low-voltage MCCs and panelboards |
25 |
355.6 mm × 304.8 mm × ≤203.2 mm |
14 in × 12 in × ≤8 in |
Deep low-voltage MCCs and panelboards |
25 |
355.6 mm × 304.8 mm × >203.2 mm |
14 in × 12 in × >8 in |
Cable junction box |
13 |
355.6 mm × 304.8 mm × ≤203.2 mm or 355.6 mm × 304.8 mm × >203.2 mm |
14 in × 12 in × ≤8 in or 14 in × 12 in × >8 in |
Reference:
IEEE 1584-2018