Circuit Breaker Specifications, Design and Application Review
IEEE C37 and IEC 62271 electrical standards govern the ratings, performance, features, and testing of circuit breakers and switchgear. The primary goal is to ensure that the circuit breakers serve the intended purpose of safely protecting the electrical distribution system. The secondary goal is to ensure that circuit breakers are electrically and mechanically interchangeable so that the electrical grid can be interconnected.
Ciruit Breake Insulated Power Frequency and Impulse Withstand Voltages
Rated Ur |
PFWV
Ud (kV) |
LIWV (pk)
Up (kV) |
Rated V (kV) |
PFWV
(kV) |
LIWV (pk)
(kV) |
||||
Com |
Iso |
Com |
Iso |
Com |
Iso |
Com |
Iso |
||
3.6 |
10 |
12 |
20 40 |
23 46 |
- |
- |
- |
- |
- |
7.2 |
20 |
23 |
40 60 |
46 70 |
4.76 |
19 |
21 |
60 |
66 |
12 |
28 |
32 |
60 75 |
70 85 |
8.75 |
36 |
40 |
95 |
105 |
17.5 |
38 |
45 |
75 95 |
85 110 |
15 |
36 |
40 |
95 |
105 |
24 |
50 |
60 |
95 125 |
110 145 |
27 |
60 |
66 |
125 |
138 |
36 |
70 |
80 |
145 170 |
165 195 |
38 |
60 |
88 |
150 |
165 |
Note: IEC also lists the IEEE ratings.
PFWF = Power Frequency Withstand Voltage
LIWV = Lighting Impulse Withstand Voltage
Com = Common
Iso = Isolating Distance
Circuit Breaker Ratings IEC 52271-100 and IEEE C37
Rating | IEC 52271-100 | IEEE C37 |
Voltage Ur (kV) | 3.6, 4.76, 7.2, 8.25, 12, 15, 17.5, 24, 27, 36, 38 |
4.76, 8.25, 15, 27, 38 |
Frequency fr (Hz) | 16 2/3, 25, 50, 60 | 50, 60 |
Nominal current Ir (A) | 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000 |
1200, 2000, 3000 |
Short-circuit current Isc (kA) | 10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80 |
Same R10 Series as IEC |
Short-time current Ik (kA) | Ik = Isc | Ik = Isc |
Peak withstand current Ip (A) | 2.5 x Isc (50 Hz) 2.6 x Isc (60 Hz) |
2.5 x Isc (50 Hz) 2.6 x Isc (60 Hz) |
Duration of short-circuit tk | 1s (option 0.5s and 2s) | 2s |
Operated sequence O = Open C = Close |
O°?3m°?CO°?3m°?CO optional: O°?0.3s°?CO°?3m°?CO O°?0.3s°?CO°?1m°?CO O°?0.3s°?CO°?15s°?CO CO°?15s°?CO |
O°?15s°?CO°?3m°?CO Option: O°?0.3s°?CO°?3m°?CO |
Mechanical operation | M1 = 2000 Option M2 = 10,000 |
1500 to 10,000 |
Electrical operation | Option for E2°?980% min. | 800% lt |
Circuit Breaker Temperature Limits per. IEC 62271 and IEEE C37
Description | Temperature Limits °C Above a 40°C Ambient |
|||
IEC 62271 |
IEEE C37 |
|||
Air |
SF6 |
Air |
SF6 |
|
Bare-copper contacts | 75 |
105 |
70 |
90 |
Silver-coated contacts | 105 |
105 |
105 |
105 |
Bare-copper connections | 90 |
115 |
70 |
100 |
Silver-plated connections | 115 |
115 |
105 |
115 |
Tin-plated connections | 105 |
105 |
105 |
105 |
Bare-copper to silver-plate | 115 |
- |
70 |
- |
Normally touched parts | 70 |
- |
50 |
- |
Not normally touched parts | 80 |
- |
70 |
- |
Reference From Table J.1 of C37.100.1 (most restrictive listed)
Capacitor Switching per IEC 62271-100 and IEEE C37
Capacitors are often applied to the electrical grid to stabilize voltages following power distributions and to improve power quality. The preferred circuit breaker for capacitor switching is one that has a low probability of restrike. If the circuit breaker is unable to successfully interrupt, the transient voltage can escalate on successive re-strikes. Therefore, the standards have set series of test procedures and ratings to help establish the circuit breakers capacitor switching capabilities. The Table below outlines the optional tests that can be conducted on breakers intended for use on capacitor circuits.
Description | IEC 62271-100 | IEEE C37 |
Capacitor switching classes |
C1 = low probability of restrike C2 = very low probability of restrike |
CO = 1 restrike/operation OK C1 same as IEC C2 same as IEC |
Cable charging breaking current Ic |
10, 25, 31.5A optional |
10, 25, 31.5A mandatory |
Single capacitor bank breaking current |
400A | 250, 400, 630, 1000, 1600A |
Back-to-back capacitor bank breaking current |
400A | 400, 630, 1000, 1600A |
Inrush making Current |
20 kA | 15, 20, and 25 kA |
Frequency of inrush current |
4.25 kHz | 1.3, 2, and 4.3 kHz |
The requirements of IEEE, for the most part, equal or exceed IEC requirements. The reason for this is user participation at IEEE meetings. Standard voting is based on individual for IEEE and by country for IEC. The Table below provides a current summary of some of the key differences between the standards.
Description | IEC | C37 |
Maximum interrupting time | Not required | 50 and 83 ms |
Short time duration | 1 second | 2 seconds |
Operating duty (basic) | O-3m-CO-3m-CO | O-15s-CO-3m-CO |
Electrical endurance | Short circuit only | 800% of It |
Normally touched parts | 70°C | 50°C |
Abnormally touched parts | 80°C | 70°C |
Copper contacts | 80°C | 75°C |
Bare-copper connections | 90°C | 70°C |
Silver connections | 115°C | 105°C |
Silver to bare copper | 115°C | 70°C |
PFWV/rated voltage 1 | 2.3 | 3.0 |
LIWV/rated voltage 1 | 4.4 | 7.9 |
Continuous current ratings | R10 series | Three listed ratings |
Voltages specifically listed | World | North America |
Single-phase asymmetrical test | Not required | Required |
Cable capacitance switching | Not required | Required |
Number of capacitor switch ratings | 1 | 5 |
Load switching | Not required | Required |
Double earth fault | Option | Not addressed |
RRRV on outdoor breakers | Same as indoor | 50% higher |
Mechanical endurance | 2000 | 1500 to 10,000 |
1 PFWV and LIWV is the average of all ratings from 3.3 to 38 kV.
Note: C37.20.2°?IEC 62271-1, 100, and 200 comparison.
C37.100.1 bare copper connections are 20°C higher than C37.20.2.
Related